WBP series power system

WBP-70

WBP-120

WBP-160

WBP-250

WBP-320

Rated power, KWe(1)

70

120

160

250

320

Gas energy input, Kcal/KWe-h(2)

3010

3000

2920

2920

2920

No. of gensets

1

1

1

1

2

Genset gas engine

Cummins 100% producer gas, 4-stroke, 1,500 RPM

- Model (aspiration(3))

G855G (NA)

GTA855G (TA)

GTA1150G (TA)

GTA1710G (TA)

GTA1150G (TA)

- No. of cylinders

6

6

6

12

6

- Displacement, L

14

14

18.9

28

18.9

Genset alternator

Stamford 1500 RPM, 415VAC, 50Hz

- Model

UC27E

UC2744H2

HC4C

HC4E

HC4C

- KVA

125

200

250

380

250

WBP series CHP system

WBP-70-CHP

WBP-120-CHP

WBP-160-CHP

WBP-250-CHP

WBP-320-CHP

- Jacket heat recovery, KWth

95

115

160

260

320

- Exhaust heat recovery, KWth

40

70

95

150

190

WBG gasifier model

WBG-120

WBG-200

WBG-250

WBG-400

WBG-500

Bio-fuel

Wood chips, briquettes and pellets, nut shells, sunflower hulls, corn cob and similar

 - Size

Chips: 20-70 mm; Briquettes: 10-70 mm; Pellets: 8-20 mm

 - Moisture

< 20%

 - Consumption, kg/h, max.

90

155

205

320

415

 - Fuel charge

Batch during gasifier operation

Typical gas composition

CO = 19 ± 3%    CO2 = 10 ± 3%     N2 – 50%      H2 = 18 ± 2%     CH4 = upto 3%

Gas temperature

300 - 500°С at oulet from gasifier, < 30°С after scrubber

Gas LHV

1,150 – 1,300 KCal/Nm3 depending on fuel type

Ash/char removal

Dry, continuous

(1) In grid-connected duty

(2) At 100% load

(3) NA – Natural aspiration, TA – Turbocharged after cooled, TI - Turbocharged inter cooled
 
For other configurations and more details, call us on +44 1462 437347 or email sales@flextechnologies.co.uk.